RESIDUAL CURRENT CIRCUIT BREAKER

Model No. JG-R001
Number of poles 1 P+N (2P), 3P+N (4P)
Rated Voltage(Un) 2P:240V 4P: 415V
Rated Current(ln) 16A,25A,32A,40A, 63A
Rated frequency 50/60 Hz
Type AC
Rated residual 30mA, 100mA,300mA
operating current( In)
Rated insulation voltage(Ui) 415V
Rated impulse 4KV
withstand voltage (Uimp)
Utilisation range temperature -5°C to 40°c
Storage temperature -25°C to 70°c
Rated making and 500A for models 16A, 25A, 32A and 40A
breaking capacity (Im) 630A for model 63A
Rated residual making and 500A for models 16A, 25A, 32A and 40A
breaking capacity(LΔm) 630A for model 63A
Rated conditional 6000A
short-circuit current (Inc)
Rated conditional residual 6000A
short-circuit current(ILl.c)
Residual current off-time ~0.1s
Terminal protection degree IP20
Endurance >=4000
Method of mounting on rail