JG2 SERIES – POWER CONTACTOR

MODEL JG2-115 JG2-150 JG2-185 JG2-225 JG2-265 JG2-330 JG2-400
FRAME 1 FRAME 2 FRAME 3 FRAME 4 FRAME 5
Rated conventional heating current (A) AC-1 200 200 275 275 315 380 450
Rational operational current (A) AC-3 380/400V AC 115 150 185 225 265 330 400
AC-4 660/690V AC 86 108 118 137 170 235 303
Power of controlled 3-phase cage motor (AC-3) Kw  380/400V AC 55 75 90 110 132 160 200
660/690V AC 80 100 110 129 160 220 280
hp 240V AC 40 50 60 75 100 125 150
415V  AC 60 75 100 125 150 150 200
480V AC 75 100 100 125 150 200 250
600V AC 75 100 100 125 150 200 300
Operating cycles (operations /h) AC-3 1200 1200 600 600 600 600 600
Electrical life (x106 operations ) AC- 3 1.2 1.2 1 1 0.8 0.8 0.8
Mechanical life (x106 operations ) 10 10 6 6 6 6 6

 

MODEL JG-2-115 JG2-150 JG2-185 JG2-225 JG-265 JG2-330 JG2-400
A 167 167 171 171 202 213 213
B 163 171 174 197 203 206 206
C 172 172 183 183 215 220 220
P 37 40 40 48 48 48 48
S 20 20 20 25 25 25 25
ɸ M6 M8 M8 M10 M10 M10 M10
f 131 131 131 131 147 147 147
M 147 150 154 170 178 181 181
H 124 124 127 127 147 158 158
L 107 107 113.5 113.5 141 145 145
X1 200-500V 10 10 10 10 10 10 15
X1 660-1000V 15 15 15 15 15 15 20
Ga 80 80 80 80 96 96 80
Ha 110~120 110~121 110~122 110~123 110~124 110~125 170~180
Spread the love